BS-V fire protection connector for use in system G3.1
Fire protection connector SML
CON-PIPSLEV-SML-PLA-DN125
Art.-no. 0893304105
EAN 4099618689703
Individual price display after login
Exclusively for trade customers
Register now and access more than 125,000 products
Fire protection connectors with intumescent insert for floor-to-floor sealing of cast iron pipes (mixed installation) in house drainage systems
Stainless-steel pipe connectors with fire protection properties for use in cast pipe systems in accordance with DIN 19522/EN 877
- In the event of a fire, the intumescent material has a foaming effect, which closes the main pipe
- End-to-end EPDM seal
- Protection against mechanical influences
- Can also be mounted in branch sections
Notice
The general fastening guidelines from the pipe manufacturers must also be observed during installation.
Application area
Product information
Datasheets(X)
Application area
The BS-V fire protection connector for use in system G3.1 serves as pipe insulation for floor-to-floor sealing of cast-iron pipes (also mixed installation) in house drainage systems.
- Installation on a straight pipe: cast iron pipe DN50 to DN150 (variant 1: Z-19.53-2711)
- Installation on a branch section: up to DN100 (variant 2: Z-19.53-2712)
- Plastic pipes to be connected, without restriction/manufacturer's reference
- Install the BS-V fire protection connector in the cast pipe branch like a "normal" connector
Instructions
- 1. Install the fire protection connector up to the stop collar of the seal on the end of the pipe that has been cut at a right angle
- 2. Push the end of the pipe or fitting into the connection until it stops
- 3. Tighten the hexagon screws alternately using a socket wrench, hand ratchet or cordless screwdriver until the two clamping heads collide; proceed with block mounting. Torque 10-20 Nm
Once the heads collide, do not tighten them further. - 4. Installing the BS ceiling strip: Place the ceiling strip above the ceiling and around the cast pipes and connectors, ensuring that there is a ≥ 20 mm overhang. Fasten using aluminium adhesive tape. Additional insulation above the ceiling
- 5. Seal the remaining gap with fire protection cement
DN nominal width | DN 125 |
Suitable for pipe (SML) | DN 125 |
Outer diameter of SML pipe | 135 mm |
Outer diameter | 155 mm |
Height | 120 mm |
Select RAL-colour code
!! NOTE: On-screen visualisation of the colour differs from real colour shade!!